Treatment and Control Programmes
Guidance
The ACOP says that the risk from exposure
to legionella should be prevented or controlled;
precautions should include the use of water
treatment techniques. The following section
on treatment programmes offers advice on how
to treat water in hot and cold water systems.
It is essential that the system is kept clean
(see section on cleaning and disinfection)
because the efficacy of the control method
(both temperature and biocide activity) may
be reduced substantially in systems that are
fouled with organic matter such as slimes
or inorganic matter such as scale.
Temperature regime
This is the traditional approach to legionella
control. It is recommended that hot water
should be stored at 60C and distributed so
that it reaches a temperature of 50C within
one minute at outlets. Care is needed to avoid
much higher temperatures because of the risk
of scalding. At 50C the risk of scalding is
small for most people but the risk increases
rapidly with higher temperatures and for longer
exposure times. However the risk, particularly
to young children or the handicapped or elderly
and to those with sensory loss, will be greater.
Where a significant scalding risk has been
identified, the use of TMVs in baths and showers
should be considered to reduce temperature.
These need to be placed as close to the point
of use as possible.
To ensure the correct function of fail-safe
TMVs, there needs to be a minimum temperature
differential between the hot and cold water
supplies and the mixed water temperature.
Users should refer to the manufacturers' operating
instructions to ensure these devices are working
safely and correctly.
Monitoring the temperature regime
As well as the routine monitoring and inspection
outlined in paragraphs
Biocide treatments
Where biocides are used to treat water systems,
they, like the temperature regime, will require
meticulous control if they are to be equally
effective. In such situations, if hot water
is not needed for other reasons (e.g. for
kitchens or laundries), there is no requirement
to store hot water at 60C (or distribute at
50C), although this is not currently permitted
in NHS premises. However, if water temperatures
are reduced, any lapses in the biocide control
regime would leave the system vulnerable.
It is, therefore, recommended that the control
system is checked at least weekly to ensure
that it is operating correctly and so continuing
to control legionella.
Chlorine dioxide
Chlorine dioxide is an oxidising biocide
capable of reacting with a wide range of organic
substances. Levels of 0.5 mg/l can, if properly
managed be achieved.
Frequency Check
Standard to meet Notes Cold Water Hot Water
Monthly sentinel taps
(see glossary)The water temperature should
be below 20C after running the water for up
to two minutes. The water temperature should
be at least 50C within a minute of running
the water. This check makes sure that the
supply and return temperatures on each loop
are unchanged, i.e. the loop is functioning
as required. If fitted, input to TMVs on a
sentinel basis: The water supply to the TMV
temperature should be at least 50C within
a minute of running the water. One way of
measuring this is to use a surface temperature
probe. Water leaving and returning to the
calorifier: Outgoing water should be at least
60C, return at least 50C. If fitted, the thermometer
pocket at the top of the calorifier and on
the return leg are useful points for accurate
temperature measurement. If installed, these
measurements could be carried out and logged
by a building management system six-monthly.
Incoming cold water inlet (at least once in
the winter and once in summer). The water
should preferably be below 20C at all times
(but see paragraph 156). The most convenient
place to measure is usually at the ball valve
outlet to the cold water storage tank annually.
Representative number of taps on a rotational
basis: The water temperature should be below
20C after running the water for two minutes.
The water temperature should be at least 50C
within a minute of running the water. This
check makes sure that the whole system is
reaching satisfactory temperatures for legionella
control, effective against planktonic and
sessile legionella in hot water systems. The
Drinking Water Inspectorate prescribes a maximum
value for total oxidants in drinking water
supplies which is the combined chlorine dioxide,
chlorite and chlorate concentration. This
should not exceed 0.5mg/l as chlorine dioxide.
There are a number of commercial systems available
that release chlorine dixoide into water systems
and it may be necessary to contact the local
company in order to check that the installations
complies with the requirements of the water
regulations and, for Scotland, the Water Supply
(Water Quality) (Scotland) Regulations and
the Private Water Supplies (Scotland) Regulations
1992, as amended. It should be noted that
maintaining total oxidant levels below 0.5mg/1
at outlets may be difficult in systems with
a low turnover of water. Suppliers of commercial
chlorine dioxide systems will need to consider
these problems and, when choosing a system,
these points should be checked to ensure that
they have been addressed satisfactorily by
the supplier.
Monitoring the chlorine dioxide regime
For most systems, routine inspection and
maintenance will usually be sufficient to
ensure control if the following areas are
checked at regular intervals and remedial
action taken when necessary, with details
of all actions being recorded:
* the quantity of chemicals in the reservior;
* the rate of addition of chlorine dioxide
to the water supply;
* on a monthly basis, the concentration of
chlorine dioxide should be measured at the
sentinel taps; The concentration should be
at least 0.1mg/1. On an annual basis, the
chlorine dioxide concentration at a representative
number of outlets; the concentration should
be at least 0.1mg/1.
Ionisation
Ionisation is the term given to the electrolytic
generation of copper and silver ions for use
as a water treatment. Copper and silver ions
concentrations maintained at 400mg/1 and 40mg/1
respectively can, if properly managed, be
effective against planktonic legionella in
hot water systems. If, however, the water
is softened, silver ion concentrations between
20-30mg/1 can also be effective, provided
a minimum concentration of 20mg/1 is maintained.
This level of silver still requires copper
ions to complete the synergy.
The application of ionisation will need to
be properly assessed, designed and maintained
as part of an overall water treatment programme.
The water supply (water quality) regulations
and private supply regulations prescribe a
maximum value for the level of copper and
silver ions in drinking water supplies. It
is important that installers of ionisation
systems are aware of the need to avoid any
breach of these regulations and maintain copper
and silver levels below the maximum allowable
concentration. The local water company may
need to be consulted to check that the installation
complies with the requirements of the water
regulations.
It should be noted that, in hard water systems,
silver ion concentrations can be difficult
to maintain due to build-up of scale on the
electrodes and the high concentration of dissolved
solids precipitating the silver ions out of
solution. For both hard and soft water, the
ionisation process is pH 7,6. The build-up
of scale and concentration of dissolved solids
therefore needs to be carefully controlled
so that suitable ion levels are consistently
maintained throughout the system. This may
need extra treatments.
Monitoring the ionisation regime
For most systems, routine inspection and
maintenance will usually be sufficient to
ensure control if the following parameters
are also monitored at regular intervals and
remedial action taken when necessary, with
details of all actions being recorded:
* The rate of release of copper and silver
unions into the water supply;
* The silver ion concentrations at sentinel
outlets should be checked monthly - this should
be at least 20ug/l at outlets;
* The measurement of silver ion concentrations
at representative taps selected on a rotational
basis once each year - this should be at least
20ug/l at outlets;
* The condition and the cleanliness of the
electrodes; and the pH of the water supply.
Ozone and UV treatment
The strategies previously described are dispersive,
i.e. they are directly effective throughout
the water system downstream from the point
of application. A number of other strategies
are available (for example, UV irradiation
or ozone). These systems are not intended
to be dispersive and are usually designed
to have their effect at, or very close to,
the point of application. This usually results
in the active ingredient not being directly
measurable in the circulating system. In large
systems, it may be necessary to use a number
of point applications of these treatments
and the system suppliers will be able to advise
appropriately.
<
Back - Next >