Management of Hot and Cold Water
Systems
Guidance
The ACOP says risks from legionella should
be identified and managed. The following section
on operation and maintenance of hot and cold
water systems offers guidance on some of the
issues which need to be addressed in order
to do this.
Commissioning and re-commissioning
Following the commissioning of a new hot
water system, the water temperature should
be measured continuously at the bottom and
the outlet of the calorifier over a typical
day. If the storage vessel is big enough to
deal with the demand, the outlet temperature
will be constant throughout the day. If the
calorifier is too small, the outlet temperature
will fall during use and remedial action may
be required, particularly if temperature is
used as a control method. If the system changes
from the original specification, this procedure
will need to be repeated.
If a calorifier or any substantial part of
a hot water system is on standby use or has
been taken out of service for longer than
1 week, the water in the calorifier should
be brought up to 60C for 1 hour before being
used; this should be measured with normal
circulating pumps operating and not with the
system in a stagnant state. If there are standby
recirculating pumps on the hot water circuits,
they should be used at least once per week.
If the system is to be treated with biocides
as a means of controlling legionella, the
biocide concentration in the system should
reach normal operational levels for at least
3 hours throughout the system, before being
used.
Operation
Cold water Cold water from the water utility
is usually delivered to consumer buildings
with a trace of active chlorine disinfectant
and fit for drinking. However, users should
not rely on this to treat the hot water system.
Where water comes from rivers, lakes, boreholes
or other sources, it needs to be pre-treated
so that it is of the same quality as the mains
supply. The Water Supply (Water Quality) Regulations
require designers and maintainers of premises
to maintain the wholesome nature of the water.
The Water Supply (Water Quality) Regulations
permit water utilities to supply water to
premises at temperatures up to 25C. In practice,
the water temperature is likely to be well
below this maximum value (in the order of
5-10C in winter and up to 20C in summer).
However, during a prolonged hot summer, the
incoming water temperature at home sites can
become abnormally warm. If the incoming water
is above 20C, the water undertaker should
be allowed to see if the cause of the high
temperature can be found and removed. If this
is not possible, the risk assessment should
reflect this increased risk and appropriate
action taken if necessary.
Hot water The water can be heated by hot water
or steam from a boiler which is passed through
a coiled heat exchanger sited inside the hot-water
storage vessel, the calorifier. Calorifiers
heated directly by gas or oil flame have been
shown to have the lowest incidence of colonisation
by legionella. The calorifier can also be
heated by electricity or by means of an electric
immersion heater within the vessel.
In a hot water system, cold water enters at
the base of the calorifier with hot water
being drawn off from the top for distribution
to user points throughout the building. A
control thermostat to regulate the supply
of heat to the calorifier should be fitted
to the calorifier near the top and adjusted
so that the outlet water temperature is constant.
The water temperature at the base of the calorifier
(i.e. under the heating coil) will usually
be much cooler than the water temperature
at the top. Arrangements should therefore
be made to heat the whole water content of
the calorifier, including that at the base,
to a temperature of 60C for one hour each
day. This period needs to coincide with the
operation of the boiler plant (or other calorifier
heat source) and is usually arranged during
a period of low demand eg during the early
hours of the morning. A shunt pump to move
hot water from the top of the calorifier to
the base is one way of achieving this. However,
it should not be used continuously except
for about one hour each day (see above). In
all cases, the operation of the pump should
be controlled by a time-clock.
Alternatively, some calorifiers are fitted
with coils extending to the base to promote
convective mixing during heating. This mixing
may not be required if using alternative treatment
methodologies.
Ideally, the calorifier will have specific
connections for the shunt pump return as low
down on the calorifier as possible. For existing
calorifiers without suitable connections,
the drain point may sometimes be used. This
should not be done before cleaning and descaling
of the calorifier, otherwise the operation
of the pump may disturb sludge or sediment.
Maintenance
Some form of scale control is desirable in
hard water areas. This is because there is
a risk of calcium being deposited at the base
of the calorifier at temperatures greater
than 60C. It is recommended that an inspection
port is fitted in the side of the calorifier
so that the cleanliness of the base can be
checked and cleaned when needed. Where one
has not been fitted, any debris in the water
at the base of the calorifier should be purged
to a suitable drain on an annual basis. The
presence of scale makes it more difficult
to generate hot water efficiently in the calorifier
or water heater and reduces the effectiveness
of any treatment or disinfection measures.
Corrosion control may be required if low-corrosion
materials (copper, plastic, stainless steel
etc) have not been used in the system.
Whenever hot taps are no longer required for
use they should be removed and cut back to
the recirculating loop. Where standby units
are provided, there should be procedures in
place to enable these units to be incorporated
into routine use. Standby pumps should be
changed over and used each week to avoid water
stagnation. Standby calorifiers should be
emptied of water and there should be specified
procedures in place to be followed before
they are brought back into use. Keeping water
softeners and filters clean is important and
best done by following the manufacturers'
recommendations. Coarse filters and strainers
should be checked and cleaned regularly to
prevent the build-up of organic contaminants.
Regular flushing of showers and taps
Before carrying out the following procedures,
consideration should be given to removing
infrequently-used showers and taps. If they
are removed, the redundant supply pipework
should be cut back, as far as possible, to
a common supply, (for example, to the recirculating
pipework or the pipework supplying a more
frequently used upstream fitting).
The risk from legionella growing in peripheral
parts of the domestic water system, such as
deadlegs off the recirculating hot water,
may be minimised by regular use of these outlets.
When outlets are not in regular use, weekly
flushing of these devices for several minutes
can significantly reduce the number of legionella
discharged from the outlet. Once started,
this procedure has to be sustained and logged,
as lapses can result in a critical increase
in legionella at the outlet. Risk assessment
may indicate the need for more frequent flushing
where there is a more susceptible population
present, e.g. hospitals, nursing homes, etc.
Where it is difficult to carry out weekly
flushing, the stagnant and potentially contaminated
water from within the shower/tap and associated
dead-leg needs to be purged to drain before
the appliance is used. It is important that
this procedure is carried out with minimum
production of aerosols, e.g. additional piping
may be used to purge contaminated water to
drain.
Automatic drain valves fitted to showers to
drain the mixer valve and shower hose after
use can produce conditions within the shower
that support the growth of legionella, and
are not recommended as a method for controlling
the risk of exposure to legionella.
<
Back - Next >