Cleaning and Disinfection
Guidance
The ACOP says the risk from exposure to legionella
should be prevented or controlled; precautions
include maintaining the cleanliness of the
system and the water in it. The following
section on cleaning and disinfection offers
guidance on how to do this in cooling systems.
The maintenance of an effective biocide regime
will provide a hostile environment for microbial
life (including legionella) and minimise biofouling.
However, the use of biocides should not be
considered in isolation but as part of the
overall water treatment programme including
the manual and chemical cleaning and disinfection
of open cooling system and, in particular,
the cooling tower.
Many cooling systems operate on a continuous
basis where process conditions preclude total
system shutdown except infrequently. Other
measures, such as side-stream filtration,
more frequent microbiological monitoring,
continuous biocide addition, etc. which are
reasonably practicable should be applied and
monitored carefully.
Disinfection, cleaning and manual de-sludging
of cooling towers should be undertaken at
least twice a year, but more frequent cleaning
may be necessary depending on local environmental
conditions such as dirty atmospheres and the
conclusions reached in the risk assessment.
Cooling systems that have a short operating
period may only need to be cleaned at the
beginning and end of that period. If, on inspection,
the system shows signs of a significant build
up of deposits or slime, then disinfection
and cleaning should be carried out. The use
of chlorine or other oxidising biocides to
disinfect the tower is an effective approach,
provided they are used correctly.
In addition to this regular disinfection,
cooling towers should always be cleaned and
disinfected before being put back into service:
* immediately before the system is first commissioned;
* after any prolonged shutdown of a month
or longer (a risk assessment may indicate
the need for cleaning and disinfection after
a period of less than one month, especially
in summer and for health care premises where
shutdown is far more than five days);
* if the tower or any part of the cooling
system has been mechanically altered;
* if the cleanliness of the tower or system
is in any doubt; and if microbiologically
monitoring indicates that there is a problem.
Routine cleaning and disinfection
Pre-cleaning disinfection The system should
be disinfected using an oxidising biocide
such as chlorine, bromine or chlorine dioxide
to minimise health risks to the cleaning staff.
This is done by adding either sodium hypochlorite
solution or chloroisocyanurate compounds available
as rapid-release tablets to achieve a measured
residual of 5 mg/l free chlorine. Sodium hypochlorite
solutions typically contain 10-12% available
chlorine and rapid-release tablets contain
50-55% available chlorine. Such products should
be handled with care and according to instructions
given by the supplier. A bio-dispersant should
also be used to enhance the effectiveness
of the chlorination.
The chlorinated water containing 5mg/I free
chlorine should be circulated through the
system for a period of 5 hours with the fan
off, maintaining a minimum of 5mg/I free chlorine
at all times. However, if the system pH value
is greater than 8.0, the measured residual
will need to be in the range 15-20mg/I free
chlorine in order to achieve the required
disinfection level. An alternative procedure
to provide more effective use of chlorine
is to introduce a heavy bleed-off for several
hours to both reduce the pH of the system
water and its chlorine demand, before carrying
out disinfection. The system should then be
de-chlorinated (see paragraph 144) and drained.
Cleaning Manual cleaning operations can then
be carried out, with all accessible areas
of the tower, etc., being adequately cleaned.
Where practicable, the packs should be removed
at least once a year and preferably every
six months. If this is not practicable, it
may be necessary to apply supplementary strategies
such as side-stream filtration, increased
monitoring, etc. Accessible areas of the tower
and its packs should be adequately washed
but cleaning methods that create excessive
spray, e.g. high-pressure water jetting, should
be avoided. If this is not possible, the operation
should be carried out when the building is
unoccupied or, in the case of permanently
occupied buildings, windows in the vicinity
should be closed, air inlet blanked off and
the area that is being water-jetted should
be tented. The area should be isolated and
consideration should also be given to other
occupied premises in the immediate areas as
well as members of the public who may be in
the vicinity during cleaning.
Cleaning staff who carry out water-jetting
should wear suitable respiratory protective
equipment such as a positive-pressure respirator
with full face-piece or a hood and blouse.
Staff who use this equipment should be adequately
trained and the equipment properly maintained
(see section on protection of personnel)
Adherent scale or other deposits on the tower
and distribution system that
have not been removed by the above method
can be dissolved using chemical descalents
carefully chosen to avoid damage to the fabric
of the system. If this is not possible, routine
inspection and testing of water quality should
be particularly through.
Finally, the system should be sluiced out
until the water going to drain is clear.
Post-cleaning disinfection On completion of
the cleaning operation, the system should
be refilled and chlorinated to maintain a
minimum level of 5 mg/1 of free chlorine for
a period of 5 hours with than fan off. This
needs to be checked hourly to ensure that
a concentration of 5mg/1 is present for the
total period. Again, the use of a bio-dispersant
will enhance the effectiveness of this chlorination.
If the system volume is greater than 5m3,
the water should be de-chlorinated, drained,
flushed and refilled with fresh water and
dosed with the appropriate start-up level
of treatment chemicals, including the biocides.
While the maintenance of a continuous minimum
residual of 5mg/1 of free chlorine for a minimum
period of 5 hours is considered the best practice,
if the downtime to conduct such a lengthy
operation is not available, some compromise
may be necessary. Under such circumstances,
it may be acceptable to shorten the pre-and
post chlorination times to increase the free
chlorine level, e.g. 50mg/1 for 1 hour or
25mg/1 for 2 hours. This should only be done
of the operators are trained in this process
because, at these levels, there is a greater
risk of damaging the fabric of the system.
The system should then be de-chlorinated,
drained, flushed and refilled with fresh water
and dosed with the appropriate start up level
of treatment chemicals, including the biocides.
Before water containing high-residual free
chlorine is discharged to drain, it should
be de-chlorinated. The usual procedure is
to add sodium thiosulphate, sodium sulphite
or sodium bisulphate as a neutraliser. The
level of free chlorine is determined by testing
and the quantity of sodium salt then is calculated.
<
Back - Next >